UPSystem
19” Rack with 400 W or 1/3/6 KW generators & batteries
When our UP-series generators are combined with the UPSystem, a blackout will trigger an instant power provision from a small battery buffer within milliseconds. The generator is able to take over within seconds performing an alarm start. Once power is restored, the system automatically switches off. This plug-and-play solution requires no manual input and offers a safe, durable, and environmentally friendly backup power option during outages.
Smart
Our unique electronic block allows the user to transform the generator into a smart grid system
Convenient
Our products are almost silent in operation, thus they are ideal for reducing noise pollution.
Pollution-free
Hydrogen fuel cells are environmentally friendly, because they only emit heat and water vapor, but no harmful emissions.
Easy to use
Our patented product design is modular and its features make it easy to transport and attach anywhere needed.
Technical parameters
| UPSystem | 400 | 1K | 3K | 6K |
|---|---|---|---|---|
| Generator power rating / System continuous power |
400 W | 1 kW | 3 kW | 6 kW |
| System peak power rating (+duration) |
2400 W 230 VAC (5 s) | 7000 W 230 VAC (1 min) | 14 000 W 230 VAC (1 min) | |
| Output power options | 1500 W 24 VDC / 230 VAC | 2000 W 24 V / 1500 W 230 VAC | 5000 W 48 V / 230 VAC | 10 000 W 48 V / 230 VAC |
| Output voltage range | 23.5–28 VDC / 230 VAC | 45–52 VDC / 230 VAC | ||
| Max output current | 70 A 24 VDC / 7 A 230 VAC | 100 A 24 VDC / 7 A 230 VAC | 100 A 48 VDC / 22 A 230 VAC | 200 A 48 VDC / 44 A 230 VAC |
| Power/current limitations | Operating at a higher power than generator power rating will start draining the battery (working time is limited depending on consumption) |
|||
| System battery | 2500 Wh | 4800 Wh | ||
| Fuel consumption | 65 g/kWh | |||
| Outer box dimensions of the cabinets (W × L × H) |
600 × 600 × 1240 mm | 600 × 860 × 1740 mm | 1000 × 846 × 2100 mm | |
| Estimate of system mass | 140 kg | 150 kg | 219 kg | ca 300 kg |
| Temperature and altitude range |
0…40°C, <2000 m from sea level | |||
| Operating lifetime | 10 000 hours at generator power rating | |||
| Ventilation options | Front-back | Sides / back / top | ||
| Features | IoT is integrated to UP400_IND, in/out dry contact (external 24 V digital control/state reading) |
IoT is integrated to UP1K_IND, in/out dry contact (external 24 V digital control/state reading) |
Possible IoT box, in/out dry contact (external 24 V digital control/state reading) |
Possible IoT box, in/out dry contact (external 24 V digital control/state reading) |
| Required gas storage for 12 hour of autonomy on H2 |
0.31 kg | 0.78 kg | 2.34 kg | 4.68 kg |
| Anything else | Higher capacity battery / multiple batteries / different output voltage / 3 phase is technically possible but might need a taller/wider cabinet | |||
| Could also have a more powerful inverter (2.4 kW) | Needs 2 inverters for max power | |||
Discover other products